Reduction technique of drop voltage and power losses to improve power quality using ETAP Power Station simulation model

Open

Reza Indra Satrio, Subiyanto

2018 AIP Conference Proceedings Vol. 1941 Conference paper Cited by 7 Quartile

Abstract

The effect of electric loads growth emerged direct impact in power systems distribution. Drop voltage and power losses one of the important things in power systems distribution. This paper presents modelling approach used to restructrure electrical network configuration, reduce drop voltage, reduce power losses and add new distribution transformer to enhance reliability of power systems distribution. Restructrure electrical network was aimed to analyse and investigate electric loads of a distribution transformer. Measurement of real voltage and real current were finished two times for each consumer, that were morning period and night period or when peak load. Design and simulation were conduct by using ETAP Power Station Software. Based on result of simulation and real measurement precentage of drop voltage and total power losses were mismatch with SPLN (Standard PLN) 72:1987. After added a new distribution transformer and restructrured electricity network configuration, the result of simulation could reduce drop voltage from 1.3 % - 31.3 % to 8.1 % - 9.6 % and power losses from 646.7 watt to 233.29 watt. Result showed, restructrure electricity network configuration and added new distribution transformer can be applied as an effective method to reduce drop voltage and reduce power losses. © 2018 Author(s).

Affiliations

Department of Electrical Engineering. Faculty of Engineering, Universitas Negeri Semarang, Kampus UNNES, Gedung E11 Lantai 1, Gunungpati Semarang, 50229, Indonesia